| System Configuration | |||
| Configuration | NetSure 531 C41-B1 | NetSure 531 C41-B2 | |
| System Capacity | 6 kW | ||
| Controller Module | M522S | ||
| Rectifier | 4× R48-2000A3 or R48-2000e3 | ||
| AC Power Distribution | 1×63A/2P | ||
| Battery Connection | 2×100A/1P | ||
| DC Power Distribution | BLVD | 2×10A/1P | 1× 63A/1P, 2× 32A/1P, 3× 16A/1P |
| LLVD | 2× 63A/1P, 2×32A/1P, 2× 20A/1P | ||
| Lightning Protection | Class C | ||
| Communication Port | Dry contact (5 way alarm output) RS232 | ||
| Optional | DC lightning protection,temperature compensation cable | ||

Rectifier NetSure 531 C41 |
|
| Configuration | Model |
| Output Power vs. Temperature at | Uin>176Vac |
| Rectifier | Normal : R48-2000A3, High-efficient: R48-2000e3 |
| Electric Parameters | Desciption |
| Input Voltage | 85Vac ~ 300Vac |
| Max Input Current | 12A |
| Efficiency | Common: >94%, High-efficient: >96% |
| Output Current | 0 ~ 42A |
| Rated Voltage | -53.5Vdc |
| Working Temperatuer | -40°C ~ +80°C, -40°C ~ +65°C full load |
| Rectifier: M522S | |
| Alarm Function: | |
| Capable of triggering audible/visual alarms for system fault and reporting the alarms to host. | |
| Up to 200 pieces of historical alarm records,and can be operated by using the keys. | |
| Alarm voice and alarm time are controllable. | |
| Battery Management Function: | |
| Automatic EQ/FC; Intelligent charge current limiting; Battery protection. | |
| Battery discharge test:10 sets of battery test data records. | |
| charge modes:timing,fast,constant current. | |
| Control Function: | |
| Rectifier power on/off; Rectifier current limiting, current sharing and voltage regulating. | |
| Battery EQ/FC/Test shifting; Battery protection. | |
| Remote Function: | |
| Remote communication/control/test/adjustment. | |
| Energy-saving Function (optional) | |
| Automatic sleep
mode. Mechanical Parameters |
|
| Mechanical Parameters | |
| Dimensions (mm) | 400(w) × 200(D) × 600(H) |
| Weight (kg) | ≤25 (excluding rectifiers) |
NetSure 531 C41 được thiết kế chủ yếu cho các hệ thống viễn thông và mạng, nơi yêu cầu nguồn điện ổn định và không gián đoạn. Các ứng dụng chính bao gồm: